300/500V CU/XLPE/OS/LSZH Instrument Cable

Short Description:

For used in control systems for analogue or digital signal transmission. suitable for outdoor use at
temperature range from -52℃ to +80℃.


  • Application: For used in control systems for analogue or digital signal transmission. suitable for outdoor use at temperature range from -52℃ to +80℃.
  • Standard & specification: Cable design comply with EN 50288-7, IEC 60228, GOST 22483- 2012, IEC 60332-3-22, IEC 61034, IEC 60754-2
  • RFQ

    Product Detail

    Design

    Cable marking-Inkjet

    Operation condition

    Product Tags

    For used in control systems for analogue or digital signal transmission. suitable for outdoor use at
    temperature range from -52℃ to +80℃.


  • Previous:
  • Next:

  • 3.1 Conductor
    Plain annealed stranded circular copper conductor in accordance
    with IEC 60228 Class 2
    3.2 Insulation
    Extruded XLPE compound comply with EN 50288-7
    Core identification(single):
    Pair: White, Black
    Triple: White, Black, Red
    3.3 Twisted core
    To form a pair, the insulated conductors twisted together
    Lay length for pair / triple:
    ≤70mm for 1mm2; ≤100mm for 1.5mm2; ≤150mm for 2.5mm2;
    3.4 Assembly and filler(optional)
    The interstices between cores filled with non-hygroscopic
    polypropylene rope to form substantially circular shape with a
    suitable binder tape
    3.5 Collective screen
    Aluminum-polyester tape shield applied on assembly core, the
    metallic side down in electrical contact with a drain wire (0.5mm2)
    3.6 Binder Tape
    Non-hygroscopic tape wrapped around the collective screen
    3.7 Outer sheath
    Extruded LSZH compound comply with EN 50288-7
    Color: Grey (Non-intrinsically safe)
    Light Blue (Intrinsically safe)
    Orange (Telecom)

    For example:
    EAC YANGER® IEC 60332-3-22 CU/XLPE/OS/LSZH 1Pair×1.5 SQMM 300/500V нг (А) – HF Project Cable Code -
    52°C~+40°C 2020 ****M
    Note: “****M” meter marking by inkjet with increased sequence with numbering
    “нг (А) – HF” at least every 1 metre appear on the cable

    Rated voltage, U0/U, V 300/500
    Rated, operating temperature range, ℃ -52~+80
    Min. installation temperature without preheating, ℃ -30
    Max. conductor temperature in service, ℃ 90
    Max. permissible short-circuit temperature,5 sec, ℃ 250
    Min. bending radius, D overall diameter of cable 15D
    Flame retardant IEC 60332-3-22
    Halogen Gas Emission IEC 60754-1, < 0.5%
    Low Smoke Emission IEC 61034-1/2
    UV resistant UL 1581
    Oil resistant IEC60811(IRM 902 – 4h at 70°C,variation ±40%)
    Oxygen Index(Sheath) ASTM D 2863
    Cold bend IEC 60811-1-4, -52℃
    Cold impact IEC 60811-1-4 & CSA C22.2 No.38-10, -52℃
    Chemical resistance Accidental